SensoIRIS T110 - Addressable Heat Detector
SensoIRIS T110 is аn addressable heat detector designed for installing in addressable fire alarm systems supporting TTE communication protocol. The detector is powered on from the panel and can be controlled via the communication protocol.
The detector SensoIRIS T110 is compatible with fire base B124.
Technical Specifications
• Operating VoltageRange: 15 - 30VDC (Nom. 27VDC)
• Max. consumption in quiescent state: <180μA@27VDC
• Max. consumption in alarm state: 6.5mA
• Class, selectable from the control panel:
A1R*, A2R, BR, CR, A1S, A2S*, BS*, CS
• Protected area*: up 35m²
• Installation height*: up 3,5m
• Output in alarm state at terminal RI (terminals 4/ 1): 7.5 mA (max)/ 7.5V
• Wire Gauge for terminals: 0.4mm2 ¸ 2.0mm2
• Relative humidity resistance: (93 ± 3)% @ 40°C
* In accordance with EN54-5